Serial Transmission Time Calculator
Estimate latency of serial communications based on baud rate and payload.
Transmission Parameters
Transmission Time
Fundamentals of Serial Data Transmission
In industrial automation, legacy protocols like Modbus RTU heavily rely on serial interfaces such as RS-232 and RS-485. Accurately calculating transmission time is vital for configuring PLC polling rates and preventing timeout errors.
The Basic Transmission Formula
The time required to send a message over a serial link depends on the total bits sent and the chosen baud rate.
Transmission Time (seconds) = Total Number of Bits รท Baud Rate
Accounting for Framing Bits
Every byte of data sent serially is encapsulated in a frame. For standard 8N1 configuration, a single 8-bit data byte actually requires 10 bits of transmission time:
- 1 Start Bit
- 8 Data Bits
- 0 Parity Bits
- 1 Stop Bit
Therefore, sending a 10-byte payload requires 100 bits on the wire. At 9600 baud, this transmission takes approximately 10.4 milliseconds.
Industrial Considerations
When calculating transmission times for protocols like Modbus RTU, you must include the entire byte stream, including slave addresses, function codes, and CRC checksums. Additionally, for half-duplex RS-485 networks, factor in the “turnaround time” (dead time) required for devices to switch between transmit and receive states, which adds latency beyond the raw baud rate calculation.